Wafr Medium-Voltage Vacuum Circuit Breakers provide reliable switching, fault interruption and protection for industrial, commercial, utility and infrastructure power-distribution systems.
The breakers use vacuum interruption technology with a stored-energy operating mechanism and are designed for installation in Wafr metal-clad switchgear or compatible medium-voltage switchgear assemblies.
Available configurations cover common Canadian 5 kV and 15 kV applications, including 4.16 kV, 12.47 kV, 13.2 kV and 13.8 kV systems.

| Parameter | Standard Ratings |
|---|---|
| Equipment class | 5 kV / 15 kV |
| Typical system voltages | 4.16 / 12.47 / 13.2 / 13.8 kV |
| Rated maximum voltage | 4.76 / 15 kV |
| Frequency | 60 Hz |
| Phases | 3 |
| Continuous current | 630 / 1200 / 2000 / 3000 / 4000 A |
| Short-circuit interrupting rating | 25 / 31.5 / 40 / 50 kA |
| 15 kV-class BIL | 95 kV |
| Interrupting medium | Vacuum |
| Configuration | Drawout |
| Operating mechanism | Stored-energy spring |
| Electrical operation | Local and remote |
| Typical control power | 125 Vdc |
| Auxiliary contacts | Configurable |
| Mechanical interlocking | Standard |
| Electrical interlocking | Standard |
Final breaker ratings are selected according to system voltage, continuous current, available fault current, protection requirements and switchgear configuration.
Configuration
Drawout, with connected, test and disconnected positions
Operating Mechanism
Stored-energy spring
Operation
Electrically operated close and trip, local and remote
Interlocking
Positive mechanical and electrical interlocking as standard
Control Power
125 Vdc typical; configurable auxiliary contacts
Product Composition
Product Features
Wafr circuit breakers can be integrated with modern numerical protective relays supporting ANSI protection functions including:
Additional protection functions are available according to the application.
Wafr Medium-Voltage Vacuum Circuit Breakers and associated switchgear configurations are certified and tested to applicable Canadian and North-American requirements, including: